Cable HS XKDCu(Al)T 630 mm² Alu 110 kV

Description

Description

Standards

  • International
    IEC 60840; IEC 62067
  • National
    HD 632 Section O

 

Applications

  • Underground distribution networks
  • Laying in tubes and directly buried
  • Arises in electrical substations
     

 

Key points

  • Low shrinkage, abrasion-resistant PE outer sheath
  • Longitudinal watertightness by swelling tapes which prevent water ingress in case of damage to the outer sheath
  • Low loss high dielectric strength XLPE insulation

 
 

Construction

  • Aluminium conductor
  • Inner semi-conductor
  • Cross-linkend PE insulation ( XLPE )
  • Outer semi-conductor
  • Semi-conductive swelling tape
  • Copper wire screen
  • Semi-conductive swelling tape
  • Metallic sheath lengthwise (Copper or Aluminium)
  • Outer PEHD sheath

 

Comment

  • Cross section from 240 mm²  to 2000 mm²  
  • Other level's tension or cross-section on request
  • NOflamm version available on request
  • 2 metallic sheaths lengthwise available: copper XKDCuT, Alu XKDAlT

Characteristics

Characteristics

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
630 mm²
Conductor diameter
30.0 mm
Diameter over insulation
64.2 mm
Outer Diameter
77.6 mm
Screen section
95 mm²
Approximate weight
6.3 kg/m

Electrical characteristics

Electrical characteristics

Operating voltage
110 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
59 kA
Max. DC resistance of the conductor at 20°C
0.047 Ohm/km
Capacity core to screen
0.212 pF/m
I max. @ 90°C-buried in trefoil joined
745 A
I max. @ 90°C-buried in trefoil spaced
760 A
I max. @ 90°C-buried in flat formation joined
690 A
I max. @ 90°C-buried in flat formation spaced
755 A
I max. @ 75°C-buried in trefoil joined
670 A
I max. @ 75°C-buried in trefoil spaced
685 A
I max. @ 75°C-buried in flat formation joined
620 A
I max. @ 75°C-buried in flat formation spaced
680 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W

Mechanical characteristics

Mechanical characteristics

Maximum tensile load during service (Tl)
1890.0 daN

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
2800 mm
Laying depth, center of system
1000 mm
Laying tube diameter
120 mm
Distance between tubes (X)
200 mm

Resources

Resources

Documentation

Construction pdf — 292.1 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close